What this code requires
CALGreen 4.505.2 requires a capillary break under concrete slabs that the building code requires to have a vapor retarder, to stop moisture from wicking up through the slab. The standard method is a 4-inch-thick base of 1/2-inch or larger clean aggregate with the vapor retarder in direct contact with the concrete. Living areas and ADU floors on grade qualify; garages and other unheated accessory slabs are exempt from the CRC vapor retarder, so they usually fall outside it. Plan-checkers look for the aggregate spec and depth called out on the foundation detail.
How to fix it
Pull the foundation detail and check for the aggregate callout
Open your foundation section drawing — typically on the structural sheets (S1 or S2). Look for the note that specifies what sits directly beneath the vapor retarder. If you see just 'vapor barrier on compacted subgrade' with no gravel layer called out, that's the gap. You need a callout showing the capillary break aggregate between the subgrade and the vapor retarder. Check every slab-on-grade detail in the set, including ADU slabs. Garage slabs are exempt from the CRC R506.3.3 vapor retarder, so 4.505.2 reaches them only when a vapor retarder is otherwise required.
Add the aggregate spec with size and depth
On the foundation section detail, add a notation that reads: '4" thick base of 1/2" or larger clean aggregate, capillary break per CALGreen Section 4.505.2.1.' The key numbers are a 4-inch-thick base and aggregate 1/2 inch or larger. Do not use pea gravel, crusher fines, or decomposed granite — the aggregate must be clean, meaning minimal fines so water can't wick through the layer. If your structural engineer's detail doesn't include it, have them add a note or issue a delta revision to the foundation section. Most engineers can turn this around in a day.
Show the correct layer sequence in the slab section
The section must show the layers in order from bottom to top: compacted native soil or engineered fill, then the 4-inch clean aggregate layer, then the vapor retarder (minimum 6-mil polyethylene or approved retarder per CRC R506.3.3, in direct contact with the concrete), then the concrete slab. If you show the vapor retarder on top of the concrete, or omit the aggregate entirely, the plan-checker will kick it back. Label each layer in the section with a leader line and text note. The plan-checker should be able to read the section and confirm code compliance without opening the specification book.
Verify the vapor retarder spec meets the companion requirement
CALGreen 4.505.2.1 requires the vapor retarder to be in direct contact with the concrete, and CRC R506.3.3 sets the retarder itself: at least 6-mil polyethylene or an approved vapor retarder, with joints lapped not less than 6 inches. If your detail calls out thinner poly or unlapped joints, update it. Some plan-checkers will check both the capillary break aggregate spec and the vapor retarder spec in the same pass, so fix both before resubmitting. Confirm your spec section (typically Division 03 or 31) also reflects the updated thickness — inconsistencies between the drawings and specs generate their own correction.
Cross-reference the detail on your architectural sheets
On the architectural floor plan (typically A1 or A2) where you show 'concrete slab on grade,' add a note or detail reference pointing to the foundation section. Something like 'Slab: see struct. detail S1/5 for CALGreen 4.505.2 capillary break.' Plan-checkers spot missing coordination notes and will write a correction even if the structural detail is correct. The cross-reference closes that gap and typically takes under ten minutes to add. If you have a CALGreen checklist sheet in your plan set (common in Orange County jurisdictions), make sure 4.505.2 is checked off there too.
Confirm your geotech report doesn't conflict with the aggregate requirement
Some geotechnical reports specify a different subbase system — for example, a structural fill with compaction specs that they argue substitutes for the aggregate layer. CALGreen 4.505.2.1 also accepts other equivalent methods approved by the enforcing agency, or a slab design specified by a licensed design professional. If your geotech or engineer takes that position, the documents must say so explicitly. If they don't, the plan-checker defaults to the 4-inch aggregate method. Review the geotech report before you resubmit and coordinate with your structural engineer if there's a conflict. Geotech-versus-structural inconsistencies are a separate correction that can add another cycle.
Take the CALGreen 4.505.2 fix steps with you
All 6 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Plan-checkers flag CALGreen 4.505.2 most often because the slab detail is incomplete, not because the contractor skipped the work. Here's the breakdown.
The most common hit is a missing aggregate callout on the foundation section. The detail shows the vapor retarder sitting directly on compacted soil, with no notation for the gravel base beneath it. The code's standard method is an aggregate layer of 1/2-inch or larger clean aggregate, 4 inches thick, which needs to appear on the drawings. If your foundation section just says "poly vapor barrier on compacted subgrade," you will get this correction.
A second scenario: the aggregate is shown but the size isn't specified. A note that says "gravel layer per CALGreen" without dimensions doesn't satisfy the plan-checker. You need the nominal aggregate size and the 4-inch depth minimum called out explicitly on the detail. Some reviewers will also want a note that the aggregate is clean — free of fines that would allow capillary action to continue through the layer.
Third: the detail exists on the structural sheets but wasn't coordinated with the architectural floor plan notes. Plan-checkers review both sheets and will flag the discrepancy if the architectural sheets show "concrete slab on grade" without referencing the capillary break detail on the structural sheets. A simple cross-reference note on A1 or A2 fixes this.
A less common but expensive situation: the project uses a post-tensioned slab system, and the geotechnical report calls for a vapor barrier but the calgreen capillary break layer was omitted from the PT slab section. The PT engineer's sheets need to show the aggregate layer too, not just the structural engineer's typical section.
The official code
CALGreen Part 11 — California Green Building Standards Code (Building Standards Commission)
Read the source →