What this code requires
CALGreen 4.503.1 requires that any gas fireplace installed in new residential construction be a direct-vent sealed-combustion type. Woodstoves and pellet stoves must meet U.S. EPA NSPS emission limits and carry a permanent certification label, and woodstoves, pellet stoves and fireplaces must also comply with applicable local ordinances, which in many areas restrict open-hearth and wood-burning units. The requirement applies to new single-family homes and low-rise residential buildings permitted under Title 24 Part 11.
How to fix it
Specify direct-vent or sealed-combustion on the fireplace schedule
On your mechanical or architectural schedule, add a dedicated fireplace fixture row. The spec must state: type (direct-vent sealed-combustion), manufacturer, model number, and vent path. 'Direct-vent sealed-combustion type' is the exact term in the code, so use it as written, not a paraphrase. Plan-checkers match your language against the code text, and an exact match speeds review. Include the BTU input rating and whether the unit is approved for installation in a zero-clearance or framed chase, since that affects the structural notes on the same sheet.
Check any open-hearth or wood-burning unit against local rules
CALGreen 4.503.1 does not itself ban wood-burning fireplaces. It requires gas fireplaces to be direct-vent sealed-combustion, requires woodstoves and pellet stoves to meet U.S. EPA NSPS limits with a permanent label, and requires woodstoves, pellet stoves and fireplaces to comply with applicable local ordinances. Many cities and air districts restrict wood-burning units in new homes. If local rules bar the unit your plans show, delete it from every affected sheet: floor plan, exterior elevation, and the mechanical schedule. Do a text search in your CAD or PDF for 'fireplace,' 'hearth,' and 'wood' to catch any stray references.
Confirm the woodstove or pellet stove model is EPA NSPS certified
If you're specifying a woodstove or pellet stove, verify it has an EPA NSPS permanent certification label before you put it on the drawings. Check the EPA's Certified Wood Heaters database to confirm the exact model number is listed. Print or save a screenshot of the EPA listing and include it in your resubmittal package. Plan-checkers will ask for this documentation; having it ready in the first resubmittal prevents a second correction cycle. The physical label must be on the unit when the inspector does the rough-in or final inspection, so confirm your supplier includes it.
Show the vent termination on the elevation drawing
Direct-vent units exhaust through a co-axial pipe terminating at the exterior wall or roof. Add the vent termination symbol and label on at least one exterior elevation sheet. Note the clearance to windows and doors per the manufacturer's installation instructions, typically 12 inches minimum to an operable opening but confirm with the specific model's listing. Label the vent type and the listed product series on the drawing. This detail helps the building inspector confirm correct clearances at rough-in and avoids a field correction that stalls your final inspection.
Add a CALGreen 4.503.1 compliance note to the cover sheet
Add a general note to your cover sheet or notes sheet citing the code explicitly. Something like: 'All gas fireplaces are direct-vent sealed-combustion type per CALGreen Section 4.503.1, 2025 California Green Building Standards Code (Title 24 Part 11).' This note signals to the plan-checker that the requirement was addressed on purpose, not overlooked. It also gives the field inspector a reference to verify against during inspection. If you have multiple fireplace locations, list each one by room and sheet reference under the note.
Cross-check the energy compliance forms for consistency
Your Title 24 Part 6 energy compliance forms (CF1R and CF2R) may also reference the fireplace. Confirm the fireplace type shown on those forms matches the mechanical schedule. Mismatches between the T24 energy forms and the mechanical drawings are a frequent second-round correction because the energy plan-checker and the building plan-checker sometimes work from different sheets. Run a final cross-check before resubmitting: search every sheet for 'fireplace' and verify each instance states direct-vent sealed-combustion.
Take the CALGreen 4.503.1 fix steps with you
All 6 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Most corrections on 4.503.1 come down to one thing: the plans show a gas fireplace without specifying that it's a direct-vent sealed-combustion type. Plan-checkers won't approve what they can't verify, and a fireplace spec that just says 'gas insert' or 'see manufacturer' gives them nothing to confirm compliance.
A second common reason is that the architectural drawings show a traditional open-hearth or wood-burning fireplace, either by habit or because the design came from an older template. CALGreen 4.503.1 does not ban them outright, but it requires fireplaces to comply with applicable local ordinances, and many local rules restrict wood-burning units in new homes. Where that applies, swapping the spec to a direct-vent gas unit is the usual fix.
Pellet stoves and woodstoves cause their own headaches. Contractors often spec these without confirming that the unit has an EPA NSPS permanent certification label. The label must be visible on the unit itself, not just in a spec sheet or cut sheet. If the model isn't EPA-certified, you're back to square one.
Less common but still seen: a remodel or addition that ties into an existing open-hearth fireplace. If the project involves new construction on the same permit, even if the fireplace is existing, plan-checkers sometimes flag it under 4.503.1 until the applicant clarifies scope. Getting ahead of this with a clear note on the plans saves a review cycle.
The official code
CALGreen 4.503.1 — 2025 California Green Building Standards Code, Title 24 Part 11 (California Building Standards Commission)
Read the source →