What this code requires
ASHRAE 62.2 is the ventilation standard that California’s Title 24 building code adopts to require a whole-house mechanical ventilation system in every new residence. The standard sets the minimum continuous or intermittent airflow rate your house needs to maintain acceptable indoor air quality, calculated based on floor area and number of bedrooms. Vented kitchen hoods must meet the airflow or capture efficiency in Energy Code Table 150.0-G (110 to 280 CFM by home size and range fuel), and each bathroom needs 50 CFM of on-demand exhaust or 20 CFM continuous. New single-family homes, ADUs, and multi-unit residential projects all fall under this requirement.
How to fix it
Calculate the required whole-house CFM
Use the total required ventilation rate formula in the 2025 Energy Code (Equation 150.0-B): required CFM = 7.5 × (number of bedrooms + 1) + 0.03 × dwelling-unit floor area in square feet, counting at least 1 bedroom. For a 3-bedroom, 1,500 sq ft home: 7.5 × (3 + 1) + 0.03 × 1,500 = 30 + 45 = 75 CFM. Write this calculation out on your M-sheets — showing your inputs and result makes the plan-checker's job easy and speeds approval.
Choose a whole-house ventilation strategy
ASHRAE 62.2 allows several approaches: a dedicated supply fan (pulls outside air into the return plenum), a dedicated exhaust fan (draws stale air out continuously), or a balanced system like an ERV or HRV. For most California climates, exhaust-only or supply-only systems are the simplest. Balanced ERV/HRV systems cost more upfront but recover energy and are often the better choice in tight, well-insulated homes. Pick your strategy before sizing equipment.
Specify the fan model, CFM, and sone rating on the M-sheets
List the manufacturer name, model number, rated CFM at the system's design static pressure, and sone rating. California's energy code limits bath fans used as the whole-house ventilator to 1.0 sone or less when running continuously. Bath fans used only for demand-controlled spot exhaust are allowed up to 3.0 sones. If your whole-house strategy uses a bath fan running on a timer, make sure it's rated at 1.0 sone or less — and call that out explicitly.
Show vented kitchen exhaust sized to Table 150.0-G
Vented range hoods must meet the airflow or capture efficiency in Energy Code Table 150.0-G, from 110 CFM (electric range, home over 1,000 sq ft) to 280 CFM (gas range, home under 1,000 sq ft); other kitchen exhaust fans, including downdrafts, need 300 CFM. Recirculating hoods that filter and return air to the kitchen don't meet this requirement — the air has to go outside. Note the duct size, termination point, and fan CFM on both the floor plan and M-sheets. If the kitchen is in an interior location with a long duct run, confirm the fan's rated CFM accounts for static pressure loss.
Confirm each bathroom has 50 CFM on-demand or 20 CFM continuous exhaust
Every bathroom (including half-baths) needs an exhaust fan ducted to the exterior: 50 CFM minimum if it runs on demand, or 20 CFM if it runs continuously. Show the fan location on the floor plan and list the model and CFM on the mechanical schedule. Confirm the duct terminates at an exterior wall cap or roof jack — not into an attic space, which is both a code violation and a moisture problem.
Add a ventilation controls note
ASHRAE 62.2 requires the whole-house system to run continuously or on a timer that provides the equivalent average airflow. If your system runs intermittently (e.g., a bath fan on a 20-minutes-per-hour timer), note on the drawings how the total run time produces the required average CFM. Many plan-checkers want to see this math spelled out, especially for timer-based strategies.
Cross-reference the Title 24 compliance documents
California requires Title 24, Part 6 compliance documents for the ventilation design as part of the permit submittal, and the whole-house airflow must later pass field verification under 150.0(o)2. Make sure the form lists the whole-house fan model, CFM, and sone rating, and that the numbers on the form match what's on your M-sheets. Discrepancies between the compliance form and the drawings are a common cause of back-and-forth with the plan-checker.
Double-check duct sealing requirements
Exhaust ducts for ASHRAE 62.2 systems must be sealed per California's energy code — all joints and connections need mastic or approved tape. Call out the duct sealing method on your drawings. If you're using a supply-fan approach pulling exterior air through the HVAC return, note how the supply-air duct connection is made airtight where it connects to the existing duct system.
Take the ASHRAE 62.2 fix steps with you
All 8 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Most ASHRAE 62.2 corrections come down to one of four things: the system isn’t shown on the plans at all, the CFM rates aren’t specified, the wrong type of fan is called out, or the plans say “ventilation per code” without the actual design numbers.
The most common miss is simply not designing the whole-house system. Kitchen range hoods and bath fans handle spot ventilation; they’re not a substitute for the continuous whole-house system the standard requires. Many contractors assume bath fans cover it. They don’t. ASHRAE 62.2 treats spot and whole-house ventilation as separate systems. If your M-sheets only show a range hood and bath fans with no dedicated whole-house ERV, HRV, or supply/exhaust fan strategy, you’re getting a correction.
The second scenario is sizing. The whole-house rate is calculated from floor area and number of bedrooms. California’s energy code uses a formula based on these inputs — roughly 7.5 CFM per occupant plus a floor-area component. If your drawings call out a 50 CFM bath fan as the whole-house solution without showing the number was derived from the formula, the plan-checker will flag it. They can’t give credit for a system that isn’t documented.
Bathroom exhaust is the third trigger. ASHRAE 62.2 sets a minimum 50 CFM for bath exhaust fans, but plans also need to show sone ratings. California’s energy code, through ASHRAE 62.2, limits whole-house and continuous fans to 1 sone and demand-controlled spot exhaust to 3 sones. If the sone rating isn’t on your drawings, the plan-checker can’t verify compliance.
The fourth scenario shows up on remodel permits most often: notes say “ventilation per ASHRAE 62.2” without specifying the fan model, CFM, or sone rating. That reads as a placeholder, not a design. Plan-checkers routinely reject it and ask for the actual numbers.
The official code
ANSI/ASHRAE Standard 62.2-2022, Ventilation and Acceptable Indoor Air Quality in Residential Buildings, as adopted by 2025 Energy Code Section 150.0(o)
Read the source →