What this code requires
CMC 504.3 is the California Mechanical Code section that requires residential kitchen range hoods to exhaust cooking vapors directly to the outdoors rather than recirculate air back into the kitchen. The hood must deliver at least 100 CFM of airflow, use smooth-wall metal ductwork, and terminate outside the building with a backdraft damper. Single-family homes, ADUs, and any residential addition that includes a new cooking appliance will hit this section during plan check.
How to fix it
Specify a ducted hood on the equipment schedule
Replace any reference to a recirculating, ductless, or charcoal-filter hood with a ducted model. On the equipment schedule or kitchen elevation note, add the make, model, and rated CFM. The CMC minimum is 100 CFM, and for new dwellings the 2025 Energy Code (Table 150.0-G) requires 110 to 280 CFM or a capture-efficiency rating, by floor area and range fuel; most residential hoods run 300 to 600 CFM, which is fine as long as the duct is sized to match the manufacturer's published requirements. Note the duct diameter required by the manufacturer, typically 6 or 7 inches for residential hoods.
Show the full duct path on a plan or section
Draw the exhaust duct route on the floor plan (dashed line above the range) and on a building section if the path goes through an attic or concealed cavity. The plan-checker needs to trace the duct from the hood collar to the exterior termination. Label the duct material and size at each change in direction. Typical routes: up through the cabinet, into the attic, out a roof cap; or up and back through the exterior wall, out a wall cap. Show both on the same sheet if the route requires it.
Call out smooth-wall metal duct material
CMC 504.3 requires the exhaust duct to be smooth-wall metal. Acceptable materials include galvanized steel and stainless steel with smooth interior surfaces. Flexible aluminum duct, semi-rigid aluminum flex, and PVC pipe are all non-compliant for range hood exhaust. Add a note to the plans: 'Kitchen exhaust duct: smooth-wall galvanized steel, [diameter] inch, per CMC 504.3.' If a transition is needed at the hood collar, the transition piece must also be smooth metal.
Show the exterior termination with a backdraft damper
Detail the termination at the exterior. A wall cap or roof cap with a built-in backdraft damper is required. Most listed wall and roof caps include the damper; confirm it is listed and note it on the plans. The cap must terminate outdoors, not into an attic, crawlspace, garage, or any interior space. Minimum clearances: 3 feet from openings into the building and 3 feet from a property line. Show the termination location on the exterior elevation.
Verify duct length against the manufacturer's published limit
The duct run length from hood collar to termination affects performance. Most residential hood manufacturers publish a maximum equivalent duct length, typically 30 to 50 feet equivalent, accounting for elbows (each 90-degree elbow typically counts as 10 feet equivalent). If your run exceeds the manufacturer's limit, you have two options: upgrade to a higher-CFM blower, or shorten the run. Note the calculated equivalent length on the plans and confirm it is within the manufacturer's specification.
Check makeup air for high-CFM hoods
Neither the 2025 CMC nor the 2025 Energy Code sets a 400 CFM makeup-air trigger for residential hoods. CMC 701.3 requires makeup air where exhaust fans or kitchen ventilation interfere with appliance operation, and the Energy Code points to CMC Chapter 7. If your hood is large and the home has gas appliances, add a note addressing makeup air and check local amendments. Typical approaches include a passive makeup air duct (a gravity damper-equipped duct from the exterior) or an interlocked supply fan.
Resubmit with a response letter noting each change
When you resubmit, include a correction response letter that cites the CMC 504.3 correction item by number and describes what you changed on which sheet. Example: 'Item 12 (CMC 504.3): Revised A4.1 to show ducted range hood model [X], 350 CFM; added duct route on A2.1 floor plan and A5.1 building section; added wall cap with backdraft damper on west elevation A3.2; duct material noted as smooth-wall galvanized steel 6-inch.' This reduces back-and-forth because the checker can find every change immediately.
Take the CMC 504.3 fix steps with you
All 7 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Plan-checkers flag CMC 504.3 for a few recurring reasons, and the corrections letter usually lands before you notice the issue.
The most common trigger is showing a recirculating hood on the plans. Recirculating hoods, the kind with a charcoal filter that blows air back into the room, are not compliant under CMC 504.3 for new construction or permitted remodels. If the kitchen elevation or equipment schedule lists a ductless or recirculating model, the plans will come back with a correction. The fix is specifying a ducted hood and showing the exhaust path all the way to the exterior.
A second common flag is missing duct routing on the plans. The plan-checker needs to see where the duct goes: through the cabinet above the range, up through a soffit or wall cavity, across the attic, and out a roof cap or wall termination. If the floor plan and sections don't show that path, the correction cites CMC 504.3. This is especially common on kitchen remodels where the designer shows the hood on the elevation but forgets to coordinate the duct route on the reflected ceiling plan or building section.
The third scenario is incorrect duct material. CMC 504.3 requires smooth-wall metal duct, not flexible duct, not PVC. Plans that call out semi-rigid or fully flexible duct for the hood exhaust will get flagged. Even if flexible duct is specified only for the last few inches of the connection, the correction will cite this section and ask for smooth-wall metal the full run.
The official code
California Mechanical Code 2025 — Chapter 5 Exhaust Systems, California Building Standards Commission
Read the source →