What this code requires
CMC 305.1 requires gas appliances installed in garages to be mounted with ignition sources at least 18 inches above the garage floor. The rule covers appliances that have open flames, pilot lights, or exposed heating elements — water heaters and furnaces are the most common. An exception exists for appliances listed as FVIR (flammable vapor ignition resistant), which are tested and certified to handle vapors near floor level without sparking an ignition.
How to fix it
Confirm whether your appliance is FVIR-listed
Check the manufacturer's listing label on the appliance or the model spec sheet. FVIR-certified water heaters will show 'FVIR' or reference ANSI Z21.10.1 in the listing. If the unit is FVIR-listed, you can note the exception on the plans and skip the pedestal requirement entirely. If no listing is shown, assume the 18-inch elevation rule applies and proceed with the pedestal detail. Most gas water heaters manufactured after 2005 are FVIR-certified by default due to federal safety requirements, but the plans still need to call this out explicitly — reviewers can't assume the listing from the appliance model alone.
Add floor elevation callout to the mechanical plan
On the mechanical or site plan sheet that shows the garage, add a note stating the appliance ignition source elevation. A callout works: 'Water heater — ignition source at 18" AFF minimum per CMC 305.1' or 'Furnace — burner at 18" AFF minimum per CMC 305.1.' AFF means above finished floor. If the appliance is FVIR-listed, write: 'FVIR-listed unit — CMC 305.1 exception applies, no elevation pedestal required.' The note must appear on the plan sheet the reviewer is checking, not just in a general notes legend that may not be referenced.
Show the pedestal or platform detail on the plan
If a pedestal is required (non-FVIR unit), include a detail or elevation view showing the platform construction. The platform only needs to raise the ignition source 18 inches above the floor — not the whole appliance cabinet. For most residential water heaters, this means a platform roughly 18 inches tall under the unit. Show the platform material — typically 2x framing with plywood top, or masonry block — the overall height, and how it's anchored to the floor or wall. If seismic strapping is also required (CPC 507.2), show the strapping to the wall on the same detail. Combining both on one detail saves a second correction round.
Address garage-to-living-space separation if applicable
If the appliance is in a room that opens to a garage — even through a door — confirm the separation meets CRC R302.6 (garage drywall) and CRC R302.5 (rated door). A utility closet that shares a wall with the garage and has an unrated door may still be treated as garage space for CMC 305.1 purposes. If the opening between the closet and garage is properly rated and sealed, note that on the plans so the reviewer sees the separation clearly. On ADU projects where the garage is being converted, this is one of the most common multi-correction sequences: 305.1 flagged alongside R302.5 and R302.6 in the same letter.
Confirm combustion air is noted on the same sheet
CMC 701.4 requires adequate combustion air for gas appliances in enclosed or semi-enclosed spaces. Plan-checkers reviewing CMC 305.1 will often also flag combustion air if it's missing from the plans. Show the combustion air source — typically louvered vents, an open garage door undercut, or a direct outdoor air connection. Getting both CMC 305.1 and 701.4 addressed on the same resubmittal avoids a back-and-forth cycle that can add another 60 days to your timeline.
Write a clear response letter keyed to the correction number
Include a written response to the corrections letter that maps to each comment number. For example: 'Comment 7 (CMC 305.1): Revised Sheet M1 — added platform detail at water heater showing 18" AFF elevation. See Sheet M1, Detail A.' Plan-checkers process resubmittals faster when responses map directly to their original comments — they're not hunting through revised sheets to find what changed. A clear letter with specific sheet and detail references can reduce the review cycle to a single round rather than the typical two or three.
Take the CMC 305.1 fix steps with you
All 6 steps in one email, so you have them on site instead of on this page.
Why you got flagged
The most common reason plan-checkers flag CMC 305.1 is that the elevation requirement simply doesn't appear on the plans. A mechanical plan shows a water heater in the garage with no floor height noted — the reviewer has no way to confirm the 18-inch rule will be met, so they write the correction.
A second common scenario involves a standard water heater being shown without any FVIR notation. If the unit isn't labeled as FVIR-listed, the reviewer defaults to requiring the 18-inch pedestal. Contractors who install FVIR-certified units but don't call that out on the plans get flagged even though the installation would comply.
Garage conversions and ADUs with mechanical rooms create a third scenario. When a garage is converted to living space, the existing water heater may end up in an adjacent utility closet that opens to the garage. Plan-checkers treat any room that communicates with the garage as subject to the same elevation requirement unless the opening is fire-rated and sealed.
Furnaces installed in garages are flagged when the combustion air supply or the burner access panel is shown at floor level. Even if the main cabinet sits on a platform, reviewers will note the correction if the plans don't show the burner elevation clearly meeting the 18-inch minimum.
The official code
California Mechanical Code (CMC) — Part 4, State-Published Edition via DGS Building Standards Commission
Read the source →