What this code requires
CPC 507.2 is the California Plumbing Code section that requires water heaters in seismic zones to be secured against earthquake movement with two straps. One strap goes in the upper third of the unit and one in the lower third — not at the very top or bottom, but within those thirds. The T&P (temperature and pressure) relief valve must discharge to the exterior of the building or to an approved receptor. Most residential and ADU permits get flagged on 507.2 when the plans don't show strap locations or the discharge line termination point.
How to fix it
Add a water heater seismic strap detail to the plumbing plans
Create a dedicated detail — typically at 1/4"=1' or 1"=1' scale — showing the water heater with both strap locations called out. The upper strap must fall within the top third of the unit's height and the lower strap within the bottom third. Label the strapping material (minimum 22-gauge galvanized steel, 1.5 inches wide per standard strap specs, or engineer-specified equivalent). If you're using prefab strap kits, note the manufacturer and model number so the plan-checker can verify compliance without having to look it up separately.
Dimension the strap heights from the base of the unit
The plan-checker needs to confirm both straps are in the correct thirds, not just that they exist. Measure the total height of the water heater (typically 50–60 inches for a standard 40-gallon tank). Divide by 3. The lower strap center must fall between 0 and H/3 from the base, and at least 4 inches above the controls. The upper strap center must fall between 2H/3 and H from the base. Call these dimensions out explicitly on the detail — don't say 'strap per code' without showing the math. Use the actual heater height from the manufacturer spec sheet, not a generic dimension.
Show the T&P valve discharge line route and termination
Trace the T&P discharge line from the valve on the side of the water heater to its termination point. The line must discharge to the exterior of the building, to a floor drain, or to an approved receptor. It cannot terminate inside a wall cavity, in the attic, or into a water heater drain pan (prohibited even when the pan has a drain). Show the pipe diameter (typically 3/4" minimum, matching the valve outlet), material (copper or CPVC are common), and the exact termination point on the floor plan or plumbing riser diagram. The air gap at the termination point is often forgotten — call it out.
Adjust strap heights if the heater sits on a raised platform
Garage installations often require the water heater to sit on an 18-inch raised platform to keep the ignition source above the floor level where flammable vapors can accumulate. When a platform is present, measure strap heights from the top of the platform surface, not from the garage floor. Update your standard detail to reflect the platform height and note it clearly on the drawing. A common mistake is using a stock detail that shows measurements from grade — it fails even when the straps end up in the right place physically, because the checker can't verify compliance from the plans alone.
Verify anchor backing in metal-stud or drywall walls
Seismic straps must attach to structural backing, not just drywall. If the water heater closet or garage wall is framed with metal studs, the strap anchor bolts need to hit framing or a backing plate. Call this out on the detail: note the stud spacing, backing material (typically 3/4" plywood or a steel backing plate), and anchor size. Wood-frame walls with standard stud spacing are generally fine with lag screws into the stud face. Metal stud walls without backing are a field problem that shows up as a correction because the plans show no backing detail.
Cross-reference the seismic strap detail on the floor plan
Plan-checkers review sets sheet by sheet. After you add the strap detail, add a call-out bubble on the floor plan at the water heater location pointing to the detail sheet and number. Something like 'See Detail A5/M1 for seismic strap and T&P discharge.' Without the cross-reference, the checker may not find the detail and flag it as missing even when it's in the set. This is one of the cheapest corrections to avoid — takes about two minutes to add the bubble.
Take the CPC 507.2 fix steps with you
All 6 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Plan-checkers flag CPC 507.2 on most water heater permits because the correction is quick to spot and easy to miss in a busy set of drawings. The most common issue: the plans show the water heater on the floor plan but don't include a detail or note specifying strap locations. California is seismic zone 4 territory throughout most of the state, which means strapping isn't optional — it's a hard requirement on every residential water heater installation. If the plans don't show strap placement in both the upper and lower thirds of the unit, the plan-checker marks it.
The second trigger is the T&P relief valve discharge. The code requires the discharge pipe to route to the exterior of the building or to an approved floor drain or receptor — not into the wall, not terminating in the attic, not discharging into a pan that has no confirmed drain path to daylight. If the plumbing plan doesn't show where that discharge line terminates, it gets flagged. Some plans show the valve itself but skip the discharge routing, which is enough for a correction.
A third scenario comes up on garage-mounted water heaters. When the heater is on a raised platform (required to keep the ignition source above the floor per fire codes), the strap heights change relative to the platform surface, not the ground. Plans that copy a standard detail from a previous job often show strap heights measured from grade, which doesn't account for the platform height. That mismatch triggers a correction even when the contractor intended to comply.
The official code