What this code requires
CBC 716.2 is the California Building Code section governing fire door assemblies in fire-rated wall and floor/ceiling assemblies. It requires that any opening in a fire-resistance-rated assembly be protected by a labeled fire door assembly rated to match the wall, equipped with self-closing hardware and a positive-latching mechanism. The rating stamped on the door label must equal or exceed the rating required for the opening, and the door frame, hardware, and glazing must all be part of a tested and listed assembly. Most commercial and multi-unit residential permits get flagged on 716.2 when doors in fire corridors, stairwells, or occupancy separation walls are specified without a label or with the wrong fire-resistance rating.
How to fix it
Cross-reference the wall assembly rating against the openings table
Before touching the door schedule, pull CBC Table 716.1(2) (Opening Fire Protection Assemblies, Ratings and Markings). Find the row matching your fire-resistance-rated wall type. The table tells you the minimum fire door assembly rating required for that opening. A 1-hour fire barrier typically requires a 45-minute or 60-minute door depending on the occupancy and wall type. A 2-hour fire wall requires a 90-minute door. The table has separate rows for fire walls, fire barriers, fire partitions, smoke barriers, and corridor walls, so look up your specific wall classification rather than assuming. Write the required rating at the top of your door schedule column before specifying individual doors so the relationship is explicit when the plan-checker reviews it.
Add a fire-rating label column to every door in the schedule
For each door opening in a fire-rated assembly, add a Label column to the door schedule. List the label type (UL 10C positive-pressure rated, UL 10B neutral-pressure, or WHI equivalent) and the fire rating (20-minute, 45-minute, 60-minute, 90-minute, or 3-hour). The label designation tells the inspector and plan-checker that the door is part of a tested and listed assembly. Do not write 'rated door per code' without specifying the label. A general note is not a schedule entry, and plan-checkers will not give you credit for it.
Specify the frame as part of the same listed assembly
The door frame, not just the door leaf, must be part of the listed assembly. A labeled door leaf installed in an unlabeled frame fails the requirement. The frame type (hollow metal, knock-down, welded, or aluminum for certain glazed assemblies) must be listed with the same testing organization as the door leaf. Add a Frame Type/Label column to the door schedule and note the listed frame series or manufacturer model number. If your hardware specification references a particular frame series, that series needs to appear in both documents.
Specify a UL-listed self-closing device in the hardware set
CBC 716.2.6.1 requires fire doors to be self-closing and positive-latching. Specify a UL-listed surface-mounted or concealed door closer in the hardware set. List the closer model number or specification series (e.g., LCN 4040XP, Norton 1600 series, Sargent 351 series) in the hardware schedule. If the door is a pair, add a door coordinator. If the design calls for a hold-open function, specify a listed electromagnetic hold-open device (e.g., Sargent 1430 series) tied into the fire alarm system, and call out that the device is fail-safe: it closes on alarm signal or power loss. A prop, wedge, or furniture hold is never permitted on a fire door.
Confirm positive-latching hardware throughout the schedule
Self-closing alone is not enough. The door must also positively latch when it closes. A latchbolt or deadlatch that engages the strike plate automatically when the door swings shut meets the requirement. Privacy latches, push-pull hardware, and friction catches do not. Specify a latchbolt set with a strike in the hardware set and note the model. If the door is also an exit door, confirm that the panic device or exit device you are specifying carries a fire-rated listing for the door rating you need, because not all exit devices come with fire ratings.
Specify listed fire-rated glazing for any vision lites or sidelites
Tempered, laminated, and wired glass are not interchangeable with listed fire-rated glazing. If your door has a vision lite or the assembly includes a sidelite, specify the glazing product by manufacturer and listing number (e.g., Pilkington Pyrostop, SaftiFirst GPX, or a listed equivalent). Note the maximum lite size per the door label listing, because fire doors have lite-size limits tied to the label rating. The glazing framing must also be listed for fire resistance. Add a Glazing column to the door schedule with the product name, listing, and lite dimensions.
Add a keyed note on the floor plan at every fire door location
Once the door schedule is complete, add a keyed note on the floor plan at each fire door location pointing to the schedule. Something like: 'Fire door assembly per door schedule, CBC 716.2. Contractor to verify label rating prior to installation.' This gives the plan-checker a direct path from the plan sheet to the schedule and avoids a second correction because the connection between the plan and the schedule was not clear.
Check for local amendments before resubmitting
Some California jurisdictions have local amendments to CBC Chapter 7 that go beyond the base code. Orange County cities may require a fire-rated door in locations where the base CBC does not, particularly in occupancy separations between Group R and Group S in mixed-use buildings. If your corrections letter cited an ordinance number alongside 716.2, call the building department before resubmitting to confirm what they want to see. If the correction is a pure 716.2 issue, the revised door schedule and hardware specification should clear it.
Take the CBC 716.2 fix steps with you
All 8 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Here is why plan-checkers flag CBC 716.2 most often.
The most common trigger is a door schedule that omits the fire-rating label entirely. A contractor will list a door as a solid-core wood door or a hollow metal door without noting the UL or Warnock Hersey label and the required rating. Plan-checkers pull the occupancy separation table, see that the wall assembly needs a 90-minute door, and find no label specified. That is an automatic correction.
A close second is a rating mismatch. The wall is specified as a 2-hour fire-resistance-rated assembly, but the door schedule calls out a 45-minute label. The rule in 716.2 ties the required door rating to the wall rating, and the openings table in CBC Table 716.1(2) lays out exactly which wall rating maps to which door rating. Reviewers check the schedule against that table on every submittal.
Hardware is the third common flag. Self-closing devices and positive-latching hardware are required by 716.2.6 for every fire door. Drawings that call out a door coordinator or a hold-open magnet without specifying a UL-listed closer, or that show a privacy latch instead of a positive-latch deadbolt, get flagged. Held-open fire doors are only allowed with listed electromagnetic hold-open devices connected to the fire alarm system.
Finally, glazing in fire doors trips up a lot of plans. Any lite kit or sidelite in or adjacent to a fire door assembly must be a listed fire-rated glazing product. Ordinary tempered glass is not an acceptable substitute. If the lite size or glazing product is not called out in the door schedule alongside the label, the plan-checker will flag it as incomplete.
The official code
California Building Standards Code, Title 24 Part 2 (CBC) — Building Standards Commission