What this code requires
CRC R302.7 requires that any enclosed usable space beneath a stairway be protected on the enclosed side with 1/2-inch gypsum board. The rule covers walls, the underside of the stair framing, and any soffits in spaces accessed by a door or access panel. Most flagged plans involve closets, storage rooms, or mechanical spaces built under stairs without the drywall spec called out on the drawings.
How to fix it
Confirm whether the under-stair space is enclosed
Check if any part of the under-stair area is accessed by a door, access panel, or fixed opening. If yes, R302.7 applies and you need to show the gypsum board protection on the drawings. Open storage under open-riser stairs or fully open spaces don't trigger this requirement — only enclosed usable spaces do. When in doubt, treat it as enclosed. A space doesn't have to be finished or habitable to count — an unfinished utility closet accessed by a door is still an enclosed usable space under the code.
Add a wall section or detail showing 1/2" gypsum board
Create a detail at 1/4"=1' or larger that shows the 1/2" (12.7 mm) gypsum board applied to the walls, the underside of the stair framing (the sloped soffit), and any horizontal soffits within the enclosed space. The detail should call out the board thickness and the fastener schedule (per Table R702.3.5 for 1/2" board on 16" framing: nails at 8" o.c. on walls and 7" on ceilings, or screws at 16" and 12"). Note whether Type X or standard gypsum board is specified. Your structural sheets or interior elevation sheets are the right place for this — wherever the plan-checker expects to see wall finish specs. If the space is large enough to show up on an interior elevation, add the call-out there too.
Update the floor plan to cross-reference the new detail
On the floor plan sheet, add a note on the under-stair space pointing to your new detail (e.g., "See Detail 1/A5 for under-stair drywall per CRC R302.7"). This cross-reference makes it easy for the plan-checker to find the spec without hunting through the drawing set. Missing cross-references are a common reason for a second round of corrections even when the detail itself is correct. Label the door or access panel on the floor plan as well — the plan-checker needs to see that you've identified it as the trigger for the enclosure rule.
Show all three protected surfaces explicitly
The code covers three surfaces in the enclosed space: (1) the side walls, (2) the underside of the stair framing — the sloped ceiling that runs parallel to the stair slope, and (3) any soffits or horizontal ceilings. A common mistake is showing drywall on the walls but omitting it on the sloped underside of the treads and risers. The plan-checker will look at all three surfaces. If your detail shows only the walls, you'll get a second correction. A cross-section view works well for this because it shows all surfaces in one view without ambiguity.
Check whether CRC R302.6 also applies
If the under-stair space shares a wall with an attached garage, CRC R302.6 applies in addition to R302.7. R302.6 requires 1/2" gypsum board on the garage side of the separation, and 5/8" Type X where dwelling space is above the garage. The two sections don't conflict — R302.7 sets 1/2" as the minimum for the enclosed under-stair surfaces; R302.6 sets the garage-side separation. The simplest fix is to spec 5/8" Type X on all surfaces, which satisfies both. Call this out clearly in the detail so the plan-checker can verify compliance with both sections in one read.
Address mechanical rooms under stairs the same way
If the under-stair space houses a water heater, furnace, or electrical panel, the same 1/2" gypsum board rule applies. These spaces get treated as utility areas with unfinished framing, and that's the source of the correction. Show the drywall on the mechanical room drawings, including any return-air chases or plenums that run through the space. If the mechanical room adjoins the garage, also apply the R302.6 garage-side separation (1/2" gypsum board, or 5/8" Type X below dwelling space). If the water heater has a flue, make sure the penetration through the drywall is fire-stopped — that's a separate but related correction.
Resubmit with a written response addressing each correction item
When you resubmit, include a written response that specifically calls out the sheet and detail number where you've addressed R302.7. Something like: "CRC R302.7: 1/2" gypsum board shown at under-stair storage room on Detail 1/A5, cross-referenced on Floor Plan A1." Plan-checkers review dozens of sets — a clear response letter cuts resubmittal time. In Orange County cities served by Anaheim Public Utilities or SCE, permit resubmittals go through the same building department process regardless of utility provider.
Take the CRC R302.7 fix steps with you
All 7 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Here's why plan-checkers flag this: the correction almost always traces back to a closet or storage space built beneath the stairs with no fire-protection detail on the plans.
The most common scenario is a coat closet or under-stair storage room that shows up on the floor plan but lacks any finish or framing call-outs on the interior elevation or wall section. The plan-checker sees an enclosed space, looks for the 1/2" gypsum board spec, and doesn't find it. That's a correction. The space could be perfectly built in the field, but if the drawings don't show it, the reviewer has to flag it.
A second common trigger is a mechanical space under the stairs — water heater, FAU, or electrical panel — that the designer treated as utility space rather than an enclosed usable space. Under-stair mechanical rooms are accessed by a door or panel, which makes them enclosed spaces under the code's definition. The 1/2" drywall requirement applies to all three surfaces: the walls, the underside of the stair framing, and any soffits.
A third pattern shows up in remodels where the original permit pre-dates the current code and the contractor is adding a door to an existing under-stair cavity. Converting open storage to an enclosed space by adding a door creates a new enclosed space under R302.7. The correction notes that the new door requires the drywall protection even if the existing structure was previously unpermitted or open.
The official code
California Residential Code R302.7 — Under-Stair Protection (2025 CRC via DGS Building Standards Commission)
Read the source →