What this code requires
CBC 1011.5.2 is the California Building Code section that sets the maximum riser height and minimum tread depth for commercial stair flights. Risers cannot exceed 7 inches tall, and treads must be at least 11 inches deep, measured horizontally from nosing to nosing. Its companion, CBC 1011.5.4, limits how much individual risers and treads can vary within a single flight, which prevents the uneven stepping surfaces that cause trips. Any occupancy served by a commercial means-of-egress stair is covered, including offices, retail buildings, apartment buildings outside the dwelling units, and mixed-use.
How to fix it
Calculate riser height from actual floor-to-floor dimensions
Start with the confirmed floor-to-floor height (structural slab to structural slab, or finish floor to finish floor once slab thickness and topping are accounted for). Divide by the number of risers you plan to use. The result must be 7 inches or less. If the math gives you 7.1 inches, you need one more riser. Do the calculation before drawing the stair section, not after, because redesigning a stair on a corrections resubmit costs you 60 days. Show the calculation in a stair schedule or notes on the plan.
Set tread depth at 11 inches minimum nosing-to-nosing
The 11-inch minimum tread depth under CBC 1011.5.2 is measured horizontally from the front face of one tread nosing to the front face of the next. This is a nosing-to-nosing measurement. With uniform nosings it equals the riser-face to riser-face run, so a 1.25-inch nosing does not let you shorten the run below 11 inches. Labeling the overall tread board width as the tread depth is a common drawing error that triggers a correction.
Verify uniformity: no more than 3/8 inch variation within a flight
Check that every riser in the flight is within 3/8 inch of every other riser in the same flight, and that every tread is within 3/8 inch of every other tread. This is especially important at landings where the slab transitions. Show the riser and tread dimensions for each step in a stair section or schedule, not just a single typical callout. If you have a non-typical riser at the top or bottom because of a landing thickness adjustment, call it out explicitly and verify it falls within the 3/8 inch tolerance.
Add a dimensioned stair section to the drawings
Include a full stair section at 1/4 inch = 1 foot or larger that shows: riser height (dimension each riser if they vary), tread depth nosing-to-nosing, nosing projection (1-1/4 inches maximum), headroom clearance (minimum 80 inches along the stair path), and floor-to-floor height with the math. A plan-checker who can read the geometry directly from the section rarely writes a correction. One who has to infer it usually does.
Confirm nosing projection and profile meet CBC 1011.5.5
CBC 1011.5.5 governs nosing shape and projection. Nosings may project no more than 1-1/4 inches beyond the tread below, and projections must be uniform. The leading edge needs a curvature or bevel of 1/16 to 9/16 inch, and a riser that slopes under the tread above may lean no more than 30 degrees from vertical. Check the nosing detail in your specs against what is drawn. A stair that meets 1011.5.2 dimensions but has a code-violating nosing gets flagged on 1011.5.5, and you will need another resubmit.
Do not use residential riser heights on commercial egress stairs
CRC R318.7.5 allows residential stairs up to 7-3/4 inch risers. CBC 1011.5.2 caps commercial stairs at 7 inches. If your project has any commercial occupancy in the egress path (Group B office, Group M retail, Group R-2 apartment stairs outside the dwelling units), the commercial cap applies to those stairs. On a mixed-use project, confirm with your plan-checker which stairways are in the commercial egress path and apply CBC 1011.5.2 to those. Do not assume that because one stair serves residential units only, it gets the residential allowance.
Cross-check stair guards and handrails while revising the section
While you are revising the stair section to address 1011.5.2, check CBC 1014 (handrails) and CBC 1015 (guards) at the same time. Plan-checkers reviewing a stair correction often look at the full stair and mark up related items. Handrail height is 34 to 38 inches above the stair nosings. Guard height is 42 inches minimum on commercial egress stairs. Catching those in the same resubmit is faster than getting a second corrections letter.
Take the CBC 1011.5.2 fix steps with you
All 7 steps in one email, so you have them on site instead of on this page.
Why you got flagged
The most common reason plan-checkers flag CBC 1011.5.2 is that the stair geometry on the drawings does not match the code minimums. A contractor submits plans with risers dimensioned at 7.5 or even 7.75 inches because that is what fits the floor-to-floor height cleanly, and the reviewer marks it up because commercial code caps risers at 7 inches. The residential allowance of 7-3/4 inches under the CRC does not carry over here.
Another common flag comes from uniformity violations. CBC 1011.5.4 limits the variation between any two risers in the same flight and between any two treads in the same flight. Designers sometimes dimension a stair that averages out correctly but allows individual steps to drift. A plan-checker who measures adjacent risers and finds more than 3/8 inch variation will mark it up, even if the average is compliant.
Mixed-use projects hit this code when the architect uses residential stair tables for stairways inside a commercial occupancy. A four-story mixed-use building with retail on the ground floor has commercial stair requirements throughout the egress path, not just on the retail floor. Using CRC R318.7.5 dimensions on a commercial egress stair will get flagged every time.
The fourth scenario is missing geometry notes. Some plan sets draw the stair correctly but do not call out the riser height, tread depth, or the nosing projection in a stair section or detail. Without those callouts, a plan-checker cannot verify compliance and will write a correction asking for dimensions.
The official code
California Building Code Chapter 10 — Means of Egress, Stair Dimensions