What this code requires
Title 24 Section 110.8(i) is the California Energy Code provision that requires a roofing product's aged solar reflectance and thermal emittance to be certified and labeled (through the Cool Roof Rating Council) whenever it is used to meet the cool roof rules, and it sets default values for uncertified products. The minimums themselves are in the prescriptive sections: 150.1(c)11 for single-family homes, 140.3(a)1A for nonresidential buildings, and 170.2 for multifamily. Each slope category and climate zone has its own threshold, or an equivalent Solar Reflectance Index (SRI). Residential reroofs that replace more than 50 percent of the roof also fall under these rules.
How to fix it
Identify your climate zone and roof slope category
Find the project’s climate zone from the CF1R energy compliance form or from the climate zone map published by the California Energy Commission at energy.ca.gov. Then measure the actual roof pitch: less than 2:12 is low-sloped, 2:12 or greater is steep-sloped. Title 24 sets separate aged solar reflectance and thermal emittance thresholds for each category (150.1(c)11 for single-family, 140.3(a)1A for nonresidential), and the thresholds further vary by climate zone. Getting both inputs right before selecting a product prevents the most common resubmit cycle on cool roof corrections.
Find a CRRC-listed product with passing aged performance values
The Cool Roof Rating Council (CRRC) maintains the rated products directory. Search by manufacturer and product name. Each listing shows both initial and aged solar reflectance plus aged thermal emittance. The aged values are what the code enforces — initial values alone are not sufficient. If your current product is not listed, or its aged reflectance falls below the required threshold for your slope category and climate zone, select a different product. You can also check the Solar Reflectance Index (SRI) as an alternate compliance path if the product has a combined SRI rating that meets the minimum.
Update the roof spec on the plans with the CRRC ID and performance values
On the roof plan or general notes sheet, update the cool roof specification to include: (1) the CRRC product ID number, (2) the product’s listed aged solar reflectance value, (3) the product’s listed aged thermal emittance value, and (4) the applicable climate zone. A note that reads “cool roof per Title 24 110.8(i)” without any of this detail will get flagged again. A note like “CRRC Product ID XXXX-XXXX, aged reflectance 0.XX, aged emittance 0.XX, steep-sloped, Climate Zone XX” gives the plan-checker everything they need to clear it. For example, a single-family steep-sloped roof in Climate Zone 10 needs at least 0.20 aged reflectance and 0.75 emittance, or SRI 16.
Regenerate the CF1R to match the updated roof product values
The CF1R (CF1R-NCB-01-E for a prescriptive newly constructed single-family home) has an input field for roof solar reflectance. That value must match what you’ve spec’d on the plans. If the CF1R was generated with the default for an uncertified product (aged reflectance 0.10, or 0.08 for asphalt shingles) but the plans now show a CRRC-rated product with a higher aged reflectance, regenerate the CF1R with the correct input and resubmit both documents together. Plan-checkers compare these two documents side by side — a mismatch triggers a correction even when the product itself would otherwise pass.
Check for local amendments stricter than state minimums
Some California cities have adopted cool roof ordinances that go beyond state minimums. Los Angeles has required higher reflectance thresholds on low-sloped commercial roofs under local ordinances. Check your city’s adopted amendments before finalizing the product selection — a product that clears the Title 24 state minimum may still fail a local amendment check. For Orange County jurisdictions, review the adopted local ordinances on the city’s building department portal before your next submittal.
Check whether an exception applies and document it explicitly
The cool roof rules have exceptions worth reviewing before you assume full compliance is required. For single-family homes, building integrated photovoltaic and building integrated solar thermal panels are exempt, and so are roof constructions weighing at least 25 lb/ft². Standard rack-mounted PV is not listed. Nonresidential roofs have their own exceptions in 140.3, including an insulation tradeoff. If an exemption applies to your project, the plans must include a specific note citing the section of the code that grants the exemption and the factual basis for it. A bare “exempt” notation without that backup will not pass.
Reference the CF2R installation certificate requirement on the plans
For residential projects, the cool roof installation must be documented on a CF2R installation compliance certificate completed by the licensed contractor after installation is done. The CF2R records the actual product installed and its CRRC ID, confirming that what went on the roof matches what was approved. At plan check, the reviewer expects the plans to note that a CF2R will be completed for the cool roof installation — it doesn’t need to be in the plan set itself, but the reference needs to be there. This requirement is frequently a follow-up correction after the reflectance spec issue is resolved.
Take the Title 24 110.8(i) fix steps with you
All 7 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Here’s why plan-checkers flag 110.8(i): most contractors include a roofing spec on the plans without linking it to a listed product that has verified aged performance data. The plan-checker opens the CRRC rated products directory, searches for the product you listed, and finds either no listing at all or a listing that shows the product doesn’t hit the aged solar reflectance threshold for your climate zone. That’s the correction — a generic “cool roof per Title 24” note without a CRRC product ID and actual aged performance numbers is never going to pass plan check.
The second common scenario is a slope category mismatch. Title 24 differentiates between low-sloped roofs (less than 2:12 pitch) and steep-sloped roofs (2:12 and above), with separate performance thresholds for each. A project spec’ing a cool roof product tested on a low-slope assembly gets flagged when the actual roof pitch is 5:12 — the tested values may not apply, and the note on the plans doesn’t clarify which slope category the product is listed under.
Climate zone errors are the third trigger. California has 16 climate zones, and the required aged reflectance levels are not the same across all of them. Many contractors copy a cool roof note from a previous project in a different climate zone without updating the performance spec. A project in Climate Zone 10 (inland Southern California) can require higher aged reflectance than one in Climate Zone 1 (far northern CA). When the energy compliance form (CF1R) and the roof spec don’t agree on the climate zone inputs, 110.8(i) gets flagged — and fixing just one document without updating the other only creates a second correction round.