What this code requires
CEC 680.22 is the California Electrical Code section that governs receptacles and GFCI protection for permanently installed swimming pools and outdoor spas. It sets minimum distance rules for where receptacles can be placed near water, requires ground-fault circuit-interrupter protection on all receptacles within 20 feet of the pool or spa edge, and mandates equipotential bonding for metal parts of pool equipment, pump motors, and structural components. Permits for new pools, spa additions, and pool equipment replacements commonly trigger a CEC 680.22 correction when the electrical plan omits bonding details or places a receptacle inside the required setback zone.
How to fix it
Pull the full corrections letter before revising
CEC 680.22 corrections often come bundled with flags on 680.23 (underwater lighting), 680.25 (feeders), and 680.26 (bonding). Read every item before you start revising sheets. Fixing 680.22 without addressing the bonding diagram means a second trip through plan check.
Draw a dimensioned bonding plan on the electrical sheet
The plan-checker needs to see a diagram, not a note. Add a pool bonding detail at 1/4"=1' or larger that shows: the #8 AWG solid copper bonding conductor (bare is fine), the bonding path connecting structural rebar, pump motor frame, light niche, metal stairs, and any metal within 5 feet of the pool edge. Label each bonded component. Note the bonding grid is continuous, not just home-run to the equipment pad. If the pool shell is fiberglass or vinyl-lined and has no rebar, note that explicitly so the reviewer does not ask.
Dimension all receptacles from the pool or spa edge
On the site plan, add a dimension string from each receptacle to the nearest inside wall of the pool or spa. CEC 680.22(A) minimums are: no receptacle within 6 feet; receptacles between 6 and 10 feet must be GFCI-protected and have a cover rated for damp or wet location; receptacles beyond 20 feet can be standard. If any receptacle falls inside 6 feet, it must be relocated. Show the new location on the revised sheet and call out the revised dimension.
Mark GFCI protection on every receptacle within 20 feet
Go through your electrical schedule and flag each receptacle within 20 feet of the pool or spa as GFCI protected. A GFCI breaker in the panel or a GFCI outlet at the first receptacle in the circuit both satisfy the code requirement. Note which method you are using on the panel schedule. The reviewer will cross-check the schedule against the site plan distances, so the numbers have to be consistent.
Call out wet- or damp-location enclosures for patio receptacles
Any receptacle between 6 and 20 feet from the pool edge needs a weatherproof cover rated for damp or wet location, depending on exposure. If the outlet is under a covered patio with no direct rain exposure, in-use covers rated damp are acceptable. Open-air patio or equipment-pad outlets need wet-location (bubble) covers. Note the enclosure rating on the electrical plan. Missing this detail is a common source of secondary corrections.
Show the equipment pad circuit and disconnect on the plan
Pool pump motors, heaters, and filter equipment need a disconnect means within sight of the equipment, per CEC 680.13. Add the disconnect location to your electrical plan and note the amperage. The pump circuit itself must be GFCI-protected under CEC 680.21, whether it is 120-volt or 240-volt and whether the motor is cord-connected or hardwired. Check the equipment nameplate and document the protection method in the panel schedule.
Verify underwater lighting circuits in the panel schedule
CEC 680.23 requires GFCI protection for underwater luminaires operating above 15 volts. Plan-checkers reviewing a CEC 680.22 correction will scan the panel schedule for the lighting circuit. If it is not labeled as GFCI-protected with a dedicated breaker, they will flag it alongside your receptacle issue. Add a note in the schedule and identify the breaker type.
Resubmit with a clouded revision block on every changed sheet
Mark every sheet you revised with a revision cloud around each change and update the revision block with the date and correction number. Reviewers in most cities have a large queue; making the corrections obvious speeds up the review. If you are using Bluebeam, the revision cloud markup tool makes this a two-minute step. No clouds means the reviewer has to find the changes themselves, which sometimes means another round.
Take the CEC 680.22 fix steps with you
All 8 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Plan-checkers flag CEC 680.22 for a handful of reasons, and the corrections letters can be frustrating because they combine electrical and structural details on the same sheet.
The most common reason is a missing bonding diagram. CEC 680.26 requires all metal within 5 feet of the pool interior wall to be bonded together, and the plan-check reviewer needs to see a detail that shows the bonding conductor size (#8 solid copper minimum), the bonding path through the structural rebar, pump motor, light fixture housing, and any metal handrails. When the electrical plan just says "bond per code" without a diagram, the reviewer sends it back.
The second common flag is a receptacle inside the 6-foot or 10-foot setback. CEC 680.22(A) requires receptacles to be at least 6 feet from the inside wall of the pool; for certain receptacle types, that rises to 10 feet. Outdoor kitchen circuits, patio lighting receptacles, and sub-panels for pool equipment all need to be located and dimensioned on the site plan. When the plan shows a receptacle "near the equipment pad" without a dimension, the reviewer applies the worst-case reading and flags it.
GFCI protection omission is the third trigger. Any single-phase, 15- or 20-amp, 125- or 250-volt receptacle within 20 feet of the pool edge must be GFCI-protected. If the electrical schedule shows a standard duplex outlet on the patio within that zone, it comes back with a red mark.
Pool light circuits are sometimes missed as well. Underwater luminaires operating above 15 volts require GFCI protection under CEC 680.23, and plan-checkers reviewing the pool electrical sheet will cite 680.22 alongside 680.23 when the lighting panel schedule does not call out GFCI breakers.
The official code
California Electrical Code (Title 24, Part 3) — Article 680, Receptacles and GFCI Requirements
Read the source →