What this code requires
CEC 210.52 is the California Electrical Code section that sets where and how many receptacle outlets are required in dwelling units. The core rule: no point along a wall in a living area can be more than 6 feet from an outlet, which means outlets must appear at least every 12 feet. Kitchen countertops need outlets within 24 inches of each end and every 4 feet along the counter run. Islands and peninsulas do not require an outlet, but if none is installed, provisions for a future one must be provided. Most residential plan corrections citing 210.52 come down to missing counter outlets or inadequate spacing shown on the electrical plan.
How to fix it
Draw receptacle locations on the electrical plan sheet
Every outlet must appear on a dedicated electrical plan sheet, not just as a note on the architectural floor plan. Use the standard receptacle symbol (a circle with two lines) and place each one at its actual wall location. The plan needs to show enough information for a plan-checker to measure spacing without guesswork. If you're submitting digitally, this means properly placed symbols, not a sticky note saying 'outlets per code.'
Verify the 6-foot wall-spacing rule in every habitable room
In every living room, bedroom, and similar habitable room (hallways have their own rule), measure from any point along a wall to the nearest receptacle. That distance cannot exceed 6 feet. The practical result is that outlets appear no more than 12 feet apart along a wall. Doorways, fireplaces, and fixed cabinets break the wall line, and any wall space 2 feet or wider counts, so a short wall between doors still needs an outlet. Go room by room and mark the worst-case span on the plan — if any gap is over 12 feet, you need another outlet in that stretch.
Cover every kitchen counter segment within 24 inches of its ends
For kitchen countertops, the rule tightens. Any counter segment 12 inches wide or wider needs an outlet within 24 inches of each end of that segment, and no more than 4 feet apart along the run. Measure each counter run independently. If your kitchen has a peninsula that turns, treat each straight section as its own run. Mark the endpoint outlets on your electrical plan and show the dimension from the end of the counter to the nearest outlet so the plan-checker can verify at a glance.
Show an outlet or a future-outlet provision at islands and peninsulas
An island or peninsula does not need a receptacle, but if you leave it off, 210.52(C)(2) requires a provision at the island for adding one later. If you do install one, it must be on or not more than 20 inches above the countertop, or in the countertop using an assembly listed for countertop use. Show the outlet or the future-outlet provision on the plan with a note indicating island/peninsula location. A receptacle on the side of the island cabinet below the countertop does not count.
Show bathroom receptacle on or adjacent to the basin
Each bathroom basin needs at least one outlet on the wall or partition adjacent to it. The outlet must be within 3 feet of the outside edge of each sink. If you have a double-sink vanity, one outlet between the sinks satisfies both as long as it falls within 3 feet of each basin edge. Show the exact wall location on the plan. Bathroom outlets also require GFCI protection under CEC 210.8 — make sure both citations are addressed if your correction letter includes both.
Add outdoor receptacle at front and rear of dwelling
Single-family homes and townhomes need at least one outdoor receptacle accessible from grade at both the front and rear of the structure. The outlet must be no more than 6.5 feet above grade. Show both locations on the site plan or exterior elevation. If the structure has an attached garage, the garage requires its own outlet separate from the exterior requirement. Outdoor and garage outlets also fall under CEC 210.8 GFCI requirements.
Add dimensions to the electrical plan to prove spacing compliance
After placing all outlets, add dimension annotations that show the distance from wall ends to the nearest outlet and the gap between adjacent outlets on counter runs. This is the fastest way to get a clean plan-check — the reviewer doesn't have to measure anything, they just read your numbers. Spend 20 minutes adding these dimensions and you'll likely cut out a full correction round.
Take the CEC 210.52 fix steps with you
All 7 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Plan-checkers flag CEC 210.52 most often when the electrical plan simply doesn't show outlet locations at all. A set of architectural sheets may show wall elevations and interior layouts, but if the electrical plan is a single-line diagram without actual receptacle placement, the plan-checker has no way to verify spacing compliance and will cite 210.52 as a correction.
The second common scenario is kitchen countertop coverage. Contractors and designers sometimes place outlets along the backsplash in a general way without confirming that no countertop is more than 24 inches from the nearest outlet at either end. A galley kitchen or a run that turns a corner is a frequent miss — one side of the turn gets an outlet, the other side doesn't, and the plan-checker measures the gap and flags it.
Islands and peninsulas catch a lot of first-time corrections too. If the floor plan shows an island but the electrical plan has neither an outlet nor a provision (box and wiring) for a future outlet, that's a straightforward citation. The fix is straightforward but requires a marked-up electrical plan showing the outlet position.
Remodels are where 210.52 corrections sneak up on people. A kitchen remodel that moves walls or extends counter runs inherits 210.52 compliance requirements on the new or altered areas. If the submitted plans don't show the full outlet layout for the remodeled zone, the plan-checker will ask for it — especially in jurisdictions like Anaheim and Irvine that do a thorough electrical review even on partial remodels.
The official code
California Building Standards Commission — California Electrical Code (Title 24, Part 3)