What this code requires
CRC R703.7 requires a corrosion-resistant weep screed at the base of any exterior stucco (cement plaster) wall assembly. The screed must be installed at the foundation line, positioned at least 4 inches above finished grade and at least 2 inches above paved surfaces like driveways or patios. It creates a drainage gap at the bottom of the stucco so moisture trapped inside the wall assembly has a path out instead of rotting the framing behind it. New single-family homes, ADUs, and additions with stucco cladding will hit this correction if the weep screed detail is missing or undersized on the plans.
How to fix it
Add a wall section showing the weep screed at the foundation line
Include a wall section detail at 1/2"=1' or 3/4"=1' scale that clearly shows the weep screed installed at or below the foundation plate line at the bottom of the stucco assembly. The detail needs to be a distinct drawing, not a note. Plan-checkers want to see the actual condition, not a reference to 'per code.'
Dimension 4 inches of clearance above unpaved grade
On the wall section, add a dimension showing the weep screed positioned at least 4 inches above the finished grade. Use the finish grade elevation as your datum, not rough or existing grade. If the grade slopes along the wall, show the dimension at the lowest point. Label the dimension line clearly: "4" MIN ABOVE FINISHED GRADE."
Call out 2 inches above paved surfaces separately
If any portion of the wall base is adjacent to a concrete slab, patio, driveway, or other paved surface, add a separate note or second condition showing the 2-inch minimum clearance above the paved surface. This is a distinct requirement from the 4-inch grade clearance, and you need to show both conditions if both apply to the project. A plan note that reads "2" MIN ABOVE PAVED SURFACE" next to the relevant wall run is usually enough if the section already covers the unpaved case.
Specify a corrosion-resistant screed material
The weep screed must be corrosion-resistant. Acceptable: plastic weep screed (most common on California residential work) or corrosion-resistant metal at least 0.019 inch (No. 26 galvanized sheet gage), with a 3-1/2-inch minimum attachment flange. Call out the material on the detail or in the general notes. Something like "WEEP SCREED: PLASTIC OR MIN. NO. 26 GA. GALVANIZED, 3-1/2" MIN. FLANGE, PER CRC R703.7.2.1" works. Bare steel or uncoated metal is not acceptable.
Show the screed profile if the reviewer asks for a detail
The code requires a weep screed of a type that lets trapped water drain to the exterior, with the WRB lapping its attachment flange and the lath ending on that flange. If your plan-check comments ask for more information, include a manufacturer cut sheet for the screed product you spec, or show the profile in section. Most reviewers are satisfied with the dimensions and material callout on the wall section without a separate cut sheet.
Address the transition at existing stucco if this is an addition
If the project is adding square footage against an existing stucco wall, add a note or detail showing how the new weep screed ties into the existing assembly at the connection point. If the existing wall has no weep screed (common on pre-1990 construction), note on the drawings that new stucco work will include a weep screed at the base of the new work only, or coordinate with the inspector about the repair scope. Do not leave this transition unaddressed in the plan set.
Confirm finish grade is shown on the site plan or grading plan
The plan-checker needs to verify your 4-inch clearance dimension against an actual grade elevation. Make sure your site plan or grading plan shows finish grade at the building perimeter. If your site plan only shows existing grade, add a note with finish grade elevation at the corners of the structure. Without that reference, the reviewer cannot confirm the 4-inch dimension holds at all walls.
Take the CRC R703.7 fix steps with you
All 7 steps in one email, so you have them on site instead of on this page.
Why you got flagged
Plan-checkers flag R703.7 most often when the wall section detail either skips the weep screed entirely or shows it without dimensioning the clearance above grade. If your architectural sheets show stucco on the exterior walls but the foundation-to-wall junction is drawn as a single line with no weep screed callout, the reviewer will cite this section and send it back. That missing detail is the single most common trigger.
The second common scenario is dimensioning. Some drawings show the screed but place it at 2 inches above grade, which meets the old standard but not the current 4-inch minimum for unpaved surfaces in the 2025 CRC. Even if you drew it to scale, a reviewer who spots the number 2" on the detail will flag it.
A third scenario shows up on remodel projects where an addition ties into an existing stucco wall. The existing wall may have had no weep screed (older construction), and the permit package does not address how the new assembly transitions at grade. The plan-checker cannot approve a new stucco scope without seeing how the drainage at the base is handled, especially if the finished grade changed with the remodel.
One more situation: projects where concrete flatwork like a patio or driveway runs up against the stucco base. R703.7 requires 2 inches of clearance above paved surfaces, which is less than the 4-inch unpaved requirement. Designers sometimes forget to distinguish these conditions on the drawings, leaving the reviewer without enough information to confirm compliance.
The official code
CRC R703.7 Exterior Plaster (Stucco), weep screeds at R703.7.2.1, 2025 California Residential Code, Chapter 7 Wall Covering