What this code requires
CRC R302.10 is the California Residential Code section that sets flame spread index (FSI) and smoke development index (SDI) limits for insulation materials and their facings. Any insulation installed in a residence — batt, blown, rigid board, or spray foam — must meet these limits, and R302.10.1 sends foam plastic insulation to Section R303. Foam plastic insulation (spray polyurethane foam, rigid EPS/XPS boards) gets the most scrutiny: left exposed after the contractor finishes the work, it fails R303.4 because it lacks the required thermal barrier separating it from the interior living space. Most single-family and ADU projects that use spray foam in attics, crawl spaces, or on foundation walls get flagged on this section when the plans do not address thermal barrier requirements.
How to fix it
Identify every insulation product on the plans
Go through your drawings and list every insulation type shown: spray foam (open or closed cell), rigid board (EPS, XPS, polyiso), batt (fiberglass, mineral wool), and any composite panels. Note where each product appears and whether it is in a location where it will be exposed — visible from the living space or accessible crawl space or attic. This inventory is what you will address in the correction response.
Add a thermal barrier over all exposed foam plastic
For any foam plastic insulation (spray foam or rigid board) that is exposed to the interior of the building, show a thermal barrier on your plans. R302.10.1 sends foam plastic to Section R303, and the standard thermal barrier under R303.4 is 1/2-inch gypsum wallboard (or 23/32-inch wood structural panel) over the foam. Show this on the relevant wall section, attic detail, or foundation detail with a note referencing R303.4. If space constraints prevent drywall — common on rim joists — check whether your foam product has a listed alternative: an intumescent coating tested to NFPA 286 or UL 1715 with a test report the manufacturer can provide. List the product name and test report number on the plans.
Confirm FSI and SDI ratings for insulation facings
Kraft-faced batts and reflective foil facings are the usual suspects. The flame spread index limit is 25 or less, and smoke development index is 450 or less for insulation installed in accessible locations. Pull the product data sheet for your insulation and confirm these ratings. Add a note to the plans: [Product name], FSI 25 or less, SDI 450 or less, per manufacturer data sheet, conforming to CRC R302.10. If you cannot confirm the rating from your product, switch to an unfaced batt in accessible locations — unfaced fiberglass and mineral wool batts generally meet the limits without issue.
Update attic and crawl space insulation details
Attics and crawl spaces that are accessible for maintenance get their own scrutiny. If you are running spray foam on the underside of roof sheathing (unvented attic assembly) or on crawl space walls, your section detail needs to call out the protection. Where the space is entered only for repairs or maintenance, R303.5.3 and R303.5.4 allow a listed ignition barrier (such as 3/8-inch gypsum board) or a foam tested per R303.6 instead of a full thermal barrier. Draw a section showing the foam layer and the barrier in front of it, and label the barrier material and thickness.
Address exceptions for specific listed foam products
Some foam plastic products have tested assemblies that are specifically listed as an alternative to the standard 1/2-inch drywall thermal barrier. These are approved under R303.6, for example specific intumescent or ignition barrier coatings tested per NFPA 286 or UL 1715. If you want to use one, show the listed product name, the applicable test standard, and the manufacturer listing report number on the plans. The plan-checker needs to verify the listing without calling you. Vague notes like approved intumescent coating will not pass — name the product.
Add a general note to the notes sheet
Put a catch-all note on your general notes sheet: All insulation facings in accessible spaces shall have a flame spread index of 25 or less and smoke development index of 450 or less per CRC R302.10. All exposed foam plastic insulation shall be protected by an approved thermal barrier per CRC R303.4. This covers any insulation locations not shown in detail and signals to the plan-checker that you have addressed the requirement globally.
Attach manufacturer data sheets to the resubmittal
When you resubmit, attach the product data sheets for any foam plastic products you are using. Include the page showing FSI and SDI ratings and any listed exception testing. Tab these so the plan-checker can find them fast. A corrections cycle runs at least 60 days — anything that makes the reviewer job one minute easier is worth doing.
Take the CRC R302.10 fix steps with you
All 7 steps in one email, so you have them on site instead of on this page.
Why you got flagged
The most common trigger is spray polyurethane foam (SPF) shown on plans without a specified thermal barrier. Plan-checkers apply R303.4 (through R302.10.1) as requiring that foam plastic not be left exposed to the building interior, and if your drawings show SPF on foundation walls, rim joists, or attic rafters with no 1/2-inch drywall or code-approved intumescent coating called out, the correction goes on the letter. It does not matter that you intend to cover it — if it is not on the plans, you get flagged.
A second scenario involves insulation facings. Kraft-faced batt insulation has a paper facing with its own FSI rating. When insulation is installed in an accessible attic or crawl space and the facing is left exposed toward the living area, that paper or foil facing must meet the flame spread limits. If the plans just say R-19 batt insulation without specifying faced versus unfaced or addressing the facing requirement in an attic or crawl space application, the plan-checker will flag it.
Rigid foam board is a third common trigger. EPS or XPS board used on the interior of a foundation wall or under a slab perimeter is foam plastic governed by R303. When a designer shows rigid foam on a detail without a thermal barrier note, the correction cites R302.10 or R303.4. The fix is usually a layer of 1/2-inch gypsum wallboard, but some jurisdictions also accept specific listed intumescent coatings if the foam manufacturer has a test report.
The official code
2025 California Building Standards Code (Title 24) — California Residential Code, adopted edition via DGS
Read the source →